Fire Door Checks for an England Fire Safety Logbook

Quarterly communal doors and yearly flat entrance doors, only where the 2022 regulations apply, with access attempts written down.

Regulation 10 of the Fire Safety (England) Regulations 2022 is about fire doors in buildings in England that contain two or more sets of domestic premises. Above 11 metres, measured to the top storey as the regulations describe, the Responsible Person checks fire doors in communal areas at least every 3 months, and uses best endeavours to check flat entrance doors at least every 12 months. The checks include self closing devices. If access to a flat is not granted during a 12 month period, the record has to include the steps taken to try to gain access. Source: https://www.legislation.gov.uk/uksi/2022/547

The Home Office publication that explains the same duties for responsible persons is https://www.gov.uk/government/publications/fire-safety-england-regulations-2022

The checks apply in England.

What to put on the building

Set height to 11 metres or taller, or to 18 metres or at least 7 storeys. Tick residential with common parts. The communal door check and the flat entrance door check then become available. Under 11 metres, or not residential, those two rows stay off. A high rise residential building still has the quarterly and yearly door duties because it is over 11 metres, and it adds the monthly lift and equipment checks described on the England fire safety logbook page.

Confirm the next communal check. The preset proposes 3 months from the last check. Confirm the next flat entrance round. The preset proposes 12 months. Best endeavours is the legal standard for flat doors, not a promise that every door was opened. When a resident does not grant access, add an access attempt line with the date, whether access was gained, and the notes on what you tried.

What the check is looking at

Regulation 10 says the checks must make sure self closing devices work. It also requires residents in buildings with common parts to be told that fire doors should be kept shut when not in use, that self closers should not be tampered with, and that faults should be reported to the Responsible Person. Information duties are not the same as the inspection dates. Keep both if they apply to the building. The logbook date tracker is the inspection side.

FireCert Clock does not certify a door, does not issue a notice, and does not tell you a door passed. You confirm the date after someone has done the check.

Serious fire safety offences can bring unlimited fines and up to 2 years' imprisonment: https://www.gov.uk/workplace-fire-safety-your-responsibilities/enforcement-appeals-and-penalties

The review checklist, which is a different duty from door checks, is the fire risk assessment review checklist.

Upload your last logbook and we fill it in for you

Upload the door check records you already keep and review the suggested dates. The steps are on upload an England logbook.

Door checks that exist only for some residential buildings

GOV.UK's Fire Safety (England) Regulations 2022 overview, read 9 Nov 2026, says that in multi occupied residential buildings over 11 metres the responsible person undertakes quarterly checks on all communal fire doors and annual checks on flat entrance doors. In every multi occupied residential building, residents get fire safety instructions and information about the importance of fire doors. High rise buildings, at least 18 metres or 7 storeys, have separate monthly checks on firefighter lifts and essential firefighting equipment. The regulations came into force on 23 January 2023. https://www.gov.uk/government/publications/fire-safety-england-regulations-2022

The Fire Safety Act clarified that the Fire Safety Order covers the structure, external walls including cladding and balconies, and flat entrance doors between domestic premises and the common parts. The 2022 regulations were made under article 24 of the Order. A commercial building that is not a multi occupied residential building does not pick up the quarterly communal door check from that overview.

The product offers the communal door row and the flat entrance row when you mark the building over 11 metres with residential common parts, and the lift row when you mark it high rise. You set those facts. An address does not set them.

What to record on each check

FeatureCommunal doorsFlat entrance doorsNot a door check
How often, where the duty appliesAt least every 3 monthsAt least every 12 monthsThe risk assessment review, which is a different duty
Scope GOV.UK statesAll communal fire doors in those buildingsFlat entrance doors in those buildingsA shop or office with no residential common parts
RecordDate, what was checked, what failedDate, and the access attempts when a flat was not reachedA tick that says "doors" with no locations
Follow upRepair. The Order still requires measures to be maintainedSame, plus another attempt where access failedFiling the 24 hour lift fault. That duty is the high rise equipment row, and you send it yourself

How to track doors without swallowing the assessment

Give communal doors their own confirmed date. Give flat entrance doors their own confirmed date. Leave both off when the building is under 11 metres or is not residential with common parts. Keep the assessment review on risk assessment review so a three month door row is not stored as if it were article 9. Upload the log on upload an England logbook. The wider log is the England fire safety logbook.

Penalties GOV.UK states, read 9 Nov 2026, remain fines up to £5,000 for minor cases and unlimited fines with up to 2 years in prison for major cases. https://www.gov.uk/workplace-fire-safety-your-responsibilities/enforcement-appeals-and-penalties

How is 11 metres measured?

The overview describes the building as over 11 metres in height. It does not, on the page read, give a measuring diagram. If you are unsure whether a block is over that line, ask the fire and rescue authority or a competent person before you turn the rows on or off. The product will not calculate height from a postcode.

Does information to residents have a countdown?

The overview requires that information in all multi occupied residential buildings. It does not give a repeat interval on the page read. Store the date you issued it if you want a reminder you have chosen. Do not present that reminder as a statutory month.

FAQ

Are flat entrance doors inspected every quarter?

No. In England, above 11 metres, communal fire doors are at least every 3 months. Flat entrance doors are at least every 12 months, on a best endeavours basis, with access attempts recorded.

What if the building is over 18 metres but has no flats?

The door duties in regulation 10 are for buildings with two or more sets of domestic premises. Leave residential with common parts unticked if that is not the building. The rows stay off.

Does best endeavours mean the date can slip with no record?

No. Keep the attempt record for any 12 month period where access was not granted, including the steps taken to try. Confirm whatever next date your schedule uses.