NFPA inspection frequency lookup

Pick a system and a task. See a typical frequency from NFPA 10, 25, 72 or 101. Use it when you add an asset if your AHJ adopted a different edition.

Look up a frequency

This table is a quick reference, not a substitute for the standard. Editions change. Your authority having jurisdiction decides which edition and which local amendments apply. FireCert Clock is not an AHJ.

Portable fire extinguishers (NFPA 10)

TaskTypical frequency
Visual inspectionMonthly (about every 30 days)
Maintenance by a qualified personAnnually
Internal maintenance, stored-pressure units needing 12-year hydroEvery 6 years
Hydrostatic test: water, wet chemical, foam, CO2Every 5 years
Hydrostatic test: dry chemical stored pressure, halogenated agentsEvery 12 years

Sprinkler systems (NFPA 25)

TaskTypical frequency
Control valves, sealedWeekly inspection; monthly if locked or electronically supervised
Gauges, wet pipe systemsInspected quarterly in recent editions
Waterflow alarm devicesTested quarterly or semiannually depending on type
Fire department connectionsInspected quarterly
Sprinklers, visible from floorInspected annually
Main drain testAnnually
Antifreeze solutionTested annually
Internal pipe assessmentEvery 5 years
Standard-response sprinklersReplace or test a sample at 50 years, then every 10 years
Fast-response sprinklersReplace or test a sample at 20 years, then every 10 years

Fire alarm systems (NFPA 72)

TaskTypical frequency
Control equipmentInspected weekly to annually by component
BatteriesTested monthly to annually by type
Initiating devicesTested per the table in the adopted edition
Notification appliancesTested annually in many editions
Interface equipmentTested annually

Emergency lighting (NFPA 101)

TaskTypical frequency
30-second functional testMonthly
90-minute discharge testAnnually

How to use a row

The lookup form above filters this table. These notes sit under it so the tool stays first. The table is a quick reference, not a substitute for the standard. Editions change. Your authority having jurisdiction decides which edition and which local amendments apply. FireCert Clock is not an AHJ. When you add an asset, pick the matching preset, then change the interval if the AHJ differs. The reminder follows the interval you saved.

Put NFPA 10 on extinguishers exactly as the table states. Visual inspection is monthly, about every 30 days. Maintenance by a qualified person is annual. Internal maintenance for stored-pressure units that need a 12-year hydro is every 6 years. Hydrostatic tests are every 5 years for water, wet chemical, foam, and CO2, and every 12 years for dry chemical stored pressure and halogenated agents. A schedule you generate on the extinguisher schedule generator should land on those same rows. Tag punches stay on tag tracking. The tag remains on the cylinder.

Put NFPA 25 on sprinklers exactly as the table states. Sealed control valves are a weekly inspection, and monthly if they are locked or electronically supervised. Wet-pipe gauges are inspected quarterly in recent editions. Waterflow alarm devices are tested quarterly or semiannually depending on type. Fire department connections are inspected quarterly. Sprinklers visible from the floor are inspected annually. The main drain test is annual. Antifreeze solution is tested annually. Internal pipe assessment is every 5 years. Standard-response sprinklers are replaced or sample-tested at 50 years, then every 10 years. Fast-response sprinklers are replaced or sample-tested at 20 years, then every 10 years. The sprinkler inspection page is where those dates become assets. A shorter slogan is not a substitute for this list.

NFPA 72 and NFPA 101 stay in the tables above. Alarm control equipment is inspected weekly to annually by component. Batteries are tested monthly to annually by type. Initiating devices follow the table in the adopted edition. Notification appliances are tested annually in many editions. Interface equipment is tested annually. Emergency lighting is a 30-second functional test monthly and a 90-minute discharge test annually. The longer lighting notes are on emergency lighting test log. Do not swap a 90-minute discharge onto an extinguisher, and do not swap a 12-year hydro onto a light.

Worked example for a mixed building, as a way to pick rows, not as a survey. One dry-chemical extinguisher: monthly visual, annual maintenance, 12-year hydro. One wet riser with locked valves: monthly valve inspection, quarterly gauges, quarterly fire department connection, annual main drain, five-year internal assessment. One emergency light: monthly 30-second test, annual 90-minute test. That is six assets if you want six reminder ladders, or fewer if one person owns a group and you accept one next date. Notices are 30, 14, 7, 3, and 1 day before the date you stored, on every plan.

Free is $0 for 1 site and 25 assets. Starter is $39 a month or $390 a year for 10 sites and 500 assets. Pro is $79 a month or $790 a year for 50 sites. Business is $149 a month or $1,490 a year for 15 seats. Yearly is 10 months, two months free. Details stay on pricing. The switch form is for a list you already keep in another tool.

Who it is for: anyone adding an asset who wants the typical frequency before calling the AHJ. Who it is not for: a legal opinion, a bid, or a city that has amended the edition. If the city uses an older edition, change the interval on the asset. The mail follows what you saved.

Put the interval on an asset

Create the site, add the asset, pick the matching preset, and set the interval if your AHJ differs. Notices land 30 days out, then 14, 7, 3 and the last day.

Turn one row into one asset name

The form filters the tables. Pick the system first, then type a word from the task if you are hunting one line, such as hydro or main drain. Read the row you land on as a task, not as a whole building. A wet pipe system can need a valve check, a gauge check, a drain test, and an internal pipe look. Those are different rows. Saving them under one asset named sprinkler forces a single next date and hides the rest in a note nobody opens on the morning a notice goes out.

Name the asset after the task and the place: Riser A main drain, or Level 3 east stair extinguisher visual. The name is what the reminder will mean months later, when the person who created it is gone. A name that only repeats a standard number does not say which floor to visit.

When the adopted edition or a local amendment disagrees with a row, edit the saved gap and write the reason in the note, including who told you. The tables are a starting point. Notices use the gap stored on the asset, including an edit you typed after reading the row. Do not leave the default in place and hope a comment in some other binder will be read in time.

If you are unsure which row applies, stop and ask the authority or the contractor who last signed the report. Do not average two rows into a day count you made up. Two assets that keep the two published rows are clearer than one asset with a blended gap. You can add the second asset when the report names the task.

Open the lookup before the extinguisher schedule generator, so the agent family you type there matches the hydro row you just read. Open it before you add a sprinkler asset or a lighting asset, so the task name matches a row instead of a slogan on a slide.

FAQ

Can I search by a word like hydro?

Yes. The lookup form filters the same table.

What if my city uses an older edition?

Change the interval on the asset. The reminder follows what you saved, not the default row.