Fire extinguisher inspection schedule generator
Enter the location and agent type. Get a schedule for monthly visual checks, annual maintenance and the next hydro window.
A tag on the cylinder is not a schedule. Type the location and the agent. The generator lays out the usual NFPA 10 pattern. Your AHJ may differ. Edit the dates before you trust them.
What you get
- Monthly visual inspection dates
- Annual maintenance by a qualified person
- The 6-year internal window for stored-pressure units that need a 12-year hydro
- The 5-year or 12-year hydro window by agent
Print it for the binder. Or create the site in FireCert Clock and add each unit as an asset so you get reminders 30, 14, 7, 3 and 1 day before each is due.
What the generator is using
The schedule generator is a form: location and agent type in, dates out. The widget stays above these notes. The dates follow the NFPA 10 pattern already on the frequency lookup. Your authority having jurisdiction can adopt a different edition. Edit the dates before you trust them. FireCert Clock is not an AHJ.
The frequencies to expect, copied from that lookup:
- Visual inspection: monthly, about every 30 days.
- Maintenance by a qualified person: annually.
- Internal maintenance for stored-pressure units that need a 12-year hydro: every 6 years.
- Hydrostatic test for water, wet chemical, foam, and CO2: every 5 years.
- Hydrostatic test for dry chemical stored pressure and halogenated agents: every 12 years.
Worked example, using those intervals and not a sample building we inspected. A dry-chemical stored-pressure unit last maintained on 15 Jan 2026 has the next annual maintenance on 15 Jan 2027. The next 12-year hydro is counted from the manufacture or previous hydro date on the cylinder, not from the annual. A water or CO2 unit uses the 5-year hydro row instead. A monthly visual is about every 30 days from the last visual you enter. If you type only one date, you get one next date. Split monthly, annual, and hydro into three assets if three people own them. One asset is enough when one person does all three and you accept one next date.
Save the row as an asset if you want mail. Free is $0 for 1 site and 25 assets, with email reminders. Starter is $39 a month or $390 a year for 10 sites and 500 assets, client emails, and AI date reading from the PDF. Pro is $79 a month or $790 a year for 50 sites, no asset cap, 5 seats, and branded reports. Business is $149 a month or $1,490 a year for 15 seats, no site cap, API, and CSV. Yearly is 10 months. Reminders are 30, 14, 7, 3, and 1 day before the due date on every plan. The card is pricing. No price here is new.
How to go from the form to a list. Run the form per location, or import a CSV of location, type, and last service. Pick the NFPA 10 preset. Confirm the hydro year against the cylinder. Upload the last ticket on Starter so the date read from the PDF can be confirmed by a person. Print the row for a binder if the inspector wants paper. The tag still hangs on the cylinder. The due date lives on the asset so you know which floor to walk.
The sibling page that carries the longer emergency-lighting notes is emergency lighting test log. NFPA 101 there is a 30-second functional test monthly and a 90-minute discharge test annually. Do not paste those intervals onto an extinguisher. Extinguishers stay on the NFPA 10 rows above. If you are leaving another schedule tool, use the switch form to move the site list.
Who it is for: a contractor or a facilities lead who already has locations and agent types and wants the next dates without building a spreadsheet formula. Who it is not for: a hydraulic design tool, or a substitute for the adopted NFPA edition. The lookup page says the same thing. The table is a starting point.
After the dates look right
Print the schedule if the binder still has to exist for the walkthrough. Then create the site and add each location as an asset so the mail does not depend on someone opening the PDF. On Free that is one site and 25 assets, which covers a small floor. A second building is the moment Starter's 10 sites and 500 assets matter. Confirm every hydro date against the metal, not against memory. A generator that says 12 years for dry chemical is repeating the lookup row. The cylinder label wins if they disagree, and you edit the asset.
Keep monthly visuals on their own cadence if the annual crew is a different company. The 6-year internal for stored-pressure units that also need a 12-year hydro is easy to drop because it is neither the monthly walk nor the hydro year. Give it a line in the same list. When the inspector asks what the dates mean, the answer is the NFPA 10 row you started from, plus the edit you made for the AHJ, plus the file on the asset.
How to fill the form so the dates stay separable
Location is a finding aid, not a nickname. Kitchen fails in a building with three kitchens. Use the floor, the stair or room, and a side, the way a stranger would walk it: Level 2, east stair, next to the electrical closet. That string becomes the asset name if you save the row, so make it specific before you generate.
Agent type comes from the label on the cylinder, not from the cabinet color and not from the last unit you typed. Dry chemical stored pressure, carbon dioxide, water, wet chemical, foam, and clean agent are separate choices because the long test year is not one family. If the label is gone, do not guess an agent just to get a date. Leave that unit off the generated list until someone identifies the cylinder.
Manufacture date is the birth date on the cylinder. Last annual maintenance is the last time a qualified person did the yearly service, which can be a different year from manufacture. Last hydrostatic test is the long test, which can be older than the last annual. Leave an optional date blank when you do not have it. A blank is safer than typing the visit day into the hydro field, because the generator will then count the long window from the wrong day.
Generate one location at a time when the agents differ. A floor of mixed agents is several runs, not one run with a stand-in type. After the dates appear, read them against the metal before you print. If the year stamped on the cylinder disagrees with the generated hydro window, edit the date. The form repeats the lookup pattern. The cylinder and the authority win when they disagree.
Print for the binder if the walk still uses paper. Then save each location as its own asset if you want mail. A printed sheet in a truck does not remind anyone. If monthly looks, yearly service, and the long test belong to different people, save them as separate assets so one completion does not paint the other clocks done.
FAQ
Does agent type change the hydro year?
Yes. Water, wet chemical, foam and CO2 commonly sit on a 5-year hydro. Dry chemical stored pressure commonly sits on 12. Confirm against the cylinder and the adopted edition.
Can I generate a whole floor?
Run the form per location, or import a CSV of units into a site and let the preset do the math.